TY - JOUR
T1 - Single-tuned passive filter (STPF) for mitigating harmonics in a 3-phase power system
AU - Ishaya, Meshack Magaji
AU - Adegboye, Oluwatayomi Rereloluwa
AU - Agyekum, Ephraim Bonah
AU - Elnaggar, Mohamed F.
AU - Alrashed, Mohammed M.
AU - Kamel, Salah
N1 - Publisher Copyright:
© 2023, The Author(s).
PY - 2023/12
Y1 - 2023/12
N2 - Numerous integrals of the fundamental frequency are known as harmonics and can be found in power systems or electrical circuitry systems. Non-linear loads occasionally drain current or contains a varying impedance with each period of the AC voltage are often responsible for power system harmonics. This can result in system overheating, system losses, and equipment or system damage. In order to achieve the IEEE 519 power quality standard, filters are routinely employed to lower harmonic levels. In this work, we designed a single tuned passive filter (STPF) to minimize harmonics of sequence 5th, 7th, 11th, 13th, 17th, and 19th in a three (3) phase power system. The measurements were taken at the point of common coupling. To test the filter performance, the system and STPF were designed in MATLAB/Simulink, and the simulated results produced without and with STPF were compared. The THDI was reduced from 14.93% down to 4.87% when STPF was connected which is within the IEEE 519-2022 standard; proving that the STPF was effective in decreasing the harmonics to the desired level.
AB - Numerous integrals of the fundamental frequency are known as harmonics and can be found in power systems or electrical circuitry systems. Non-linear loads occasionally drain current or contains a varying impedance with each period of the AC voltage are often responsible for power system harmonics. This can result in system overheating, system losses, and equipment or system damage. In order to achieve the IEEE 519 power quality standard, filters are routinely employed to lower harmonic levels. In this work, we designed a single tuned passive filter (STPF) to minimize harmonics of sequence 5th, 7th, 11th, 13th, 17th, and 19th in a three (3) phase power system. The measurements were taken at the point of common coupling. To test the filter performance, the system and STPF were designed in MATLAB/Simulink, and the simulated results produced without and with STPF were compared. The THDI was reduced from 14.93% down to 4.87% when STPF was connected which is within the IEEE 519-2022 standard; proving that the STPF was effective in decreasing the harmonics to the desired level.
UR - http://www.scopus.com/inward/record.url?scp=85177745537&partnerID=8YFLogxK
U2 - 10.1038/s41598-023-47614-7
DO - 10.1038/s41598-023-47614-7
M3 - Article
C2 - 38007548
AN - SCOPUS:85177745537
SN - 2045-2322
VL - 13
JO - Scientific Reports
JF - Scientific Reports
IS - 1
M1 - 20754
ER -